ELECTRONIC CONTROLLERS
FOR ELEVATORS
HANDHELD TERMINAL T51FA
CONTROLES S.A.
Electrónica Industrial y Telecomunicaciones
Avenida Rivera 3314
11300 Montevideo
Uruguay
Tel.: +598 (2) 622 0651
Fax.: +598 (2) 622 2048
E-mail: info@controles.com
www.controles.com
GENERAL INFORMATION
T51FA is a useful tool for installation and maintenance people working with the CEA51FA family.
T51FA connects directly to a port in the controller and displays all the configuration parameters, logged events and counters. Some parameters can be changed by simple orders at the T51FA keyboard. This is particularly convenient to define operational time parameters when installing the controller or to modify accessibility options for user convenience.
NOTE: major changes at the installation site should be done using the configuration software CEA51FA-PCW running in a laptop PC, or else unskilled personnel can be instructed to take out of the socket the CEA51FA parameters memory (93LC66) and reinstall another one previously configured at the company’s engineering offices.
T51FA is a modified QTERM-J10 terminal from QSI Corp., 24 keys, EIA232 version, modified for TTL interfase. It connects directly to the TTL port at the CEA51FA. 5Vdc power supply is present at the port.
T51FA CONFIGURATION
T51FA parameters according to the specific needs are already loaded:
- auto wrap off
- auto scroll off
- auto line feed off
- cursor off
- power-on setup: only contrast adjust
To perform the Power-on Setup follow these steps:
- hold down ENTER key and connect the T51FA to the TTL port at the CEA51FA.
- keep the key pressed until the software version appears at the display.
- set the desired display contrast using the 1 (up) or 2 (down) keys. When the display is at a contrast you like, press the 3 (validate) key
DISPLAYING THE CEA51FA CONFIGURATION
Push 1 key. The display shows:
- controller model
- software version
- series number
- car number
- system identification
Push 2 key. The display shows:
- number of landings
- function (isolated, slave, master, external call
- operation (type of dispatch)
- rest station
- emergency station
- principal and secondary stations (only for master)
- position detection system
Push 3 key. The display shows:
- door type
- door state when resting
- door zone
- door delay
Push 4 key. The display shows the designation of the landings.
Push 5 key. The display shows the numeric code of each relay at the base card.
Push 6 key. The display shows the numeric code of each relay at the expansion card.
Push 7 key. The display shows the numeric code of each auxiliary relay, the total count of operations and the total time in operation.
Push 8 key. The display shows door selection for each landing.
Push 9 key. The display shows:
- releveling condition
- supervisory port
- code for digital indicators
- code for auxiliary outputs
Push 0 key. The display shows the call rejection state for the first landing. Each landing condition can be accessed and viewed pushing (up) or ¯ (down) keys.
Push F1 key. The display shows the first timer. Each timer can be accessed and viewed pushing F1 (up) or F2 (down) keys. The following list shows the code for each timer and its meaning.
Code Meaning
TTRA travel time
TALA time to alarm with no manual safety
TBUZ tolerance to attendant
TWAI floor time
TFRE time to rest state
TAUH high speed auxiliary
TLOW time wait before going to the lowest landing
TDEL delayed stop
TDOO door operation
TCAR car passenger preference
TAUL low speed auxiliary
TAUX generic auxiliary
TSTA power start auxiliary
TCHI landing chime
TGEN dc generator
TINH auxiliary for position system 1.51
Push F4 key. The display shows:
LOL lowest landing
HIL highest landing
ADV advanced door-open (0/1: normal/advanced)
PSD door rest state at duplex principal station (0/1: open/closed)
SSD door rest state at duplex secondary station (0/1: open/closed)
DCT number of door-close trials
DOT number of door-open trials
DSS door safety switch (0/1: single/double switch)
FCC number of false car calls
CML number of accepted car calls at minimum load
FDO forced door-open (0/1: opens if call/opens always)
MODIFYING THE CONFIGURATION
When the display shows a timer its time definition can be changed pushing or ¯ keys.
When the display shows the call rejection state for a landing:
- car call rejection state can be changed pushing > key
- down hall call rejection state can be changed pushing < key
- up hall call rejection state can be changed pushing , key
The changes are operational once entered, but they are not saved to the parameters memory.
To save all changes: push ENTER key. The controller will restart.
To quit without saving: push any 1 to 9 key or restart the controller.
RESTARTING THE CONTROLLER
Push DEL key to restart the system. The display shows:
CEA51FA Controller
Configurable
READING THE LIST OF EVENTS
Each event is shown in a single line, as follows:
- event index (1 to 50, 1 is the newest)
- event code (see table)
- car position at that time
Push F3 key. The display shows last registered event. Each event at the list can be accessed and viewed pushing (up) or ¯ (down) keys. Four lines are shown at a time.
Event codes:
Code Description
TT Travel time between position detectors too long
MS Manual safety =0 for a time longer than TALA
MF Manual safety fails (goes to 0) while car is running
DC Door close failure
DO Door open failure
AF Automatic safety fails (goes to 0) while car is running
EX Upper and lower end flags are detected simultaneously
HT Motor temperature failure
PF Phase loss or phase reversal failure
CF Configuration fail :the controller is not properly configured
ST Start: power is applied to the controller
CC Configuration change
To erase the whole list that is being accessed push ENTER key. The display shows
No events